9200B Signal Processor Features: |
|---|
Display: |
Type: 2 lines of 20 characters, Backlit LCD |
Character Size: 0.3″ nominal |
Isolated 4-20 Ma Analog Output: |
Type: Isolated Current Sourcing |
Resolution:12 bit |
Update Rate: 1 update/sec minimum |
Maximum Load: 1000 ohms (at nominal line voltage) |
Averaging: User entry of damping constant to cause a smooth control action. |
Isolated Totalizer Pulse Output: |
Pulse Output Form: Open Collector |
Maximum On Current: 25 mA |
Maximum Off Voltage: 30 VDC |
Saturation Voltage: 1.0 VDC |
Maximum Off Current: 0.1 mA |
Pulse Duration: 10 mSec or 100 mSec |
Pulse Output Buffer: 256 |
Fault Protection |
Reverse polarity: Shunt Diode |
Relay Outputs: |
The relay outputs are menu assignable to (Individually for each relay) Low Rate Alarm, Hi Rate Alarm, Prewarn Alarm, Preset Alarm or General purpose warning (security). |
Number of relays: 4 |
Contact Style: Form C contacts |
Contact Ratings: 5 amp, 240 VAC or 30 VDC |
Auxiliary Dc Supply With High Current Capability: |
24 VDC 420 mA (600 mA Peak) |
Power Input: |
110 VAC Power: 85-127 Vrms, 50/60 Hz (11.0 VA) |
220 VAC Power: 170-276 Vrms, 50/60 Hz (11.0 VA) |
Environmental: |
Operating Temperature: 0ºC to +50ºC |
Storage Temperature: -40ºC to +85ºC |
Humidity: 0-95% Non-condensing |
Materials: U.L. approved |